GDF Technologies repairs APC, Eaton, Vertiv, Tripp Lite and other UPS systems across Canada, from rack and tower units to large three-phase systems. Call 514-252-8324, 24/7: rapid dispatch, a technician is on site within 1 to 3 h in the Montreal area, the same day in Quebec City, Toronto and Ottawa, and within 24 to 48 hours elsewhere. Smaller rack and tower units can come to our bench in Montreal.

24/7
service line
Same day
Montreal, Quebec City, Toronto, Ottawa
24 to 48 h
elsewhere in Canada
4 business hours
to a written quote
At a glance

UPS repair at a glance

Brands

APC and Schneider Electric, Eaton and Powerware, Vertiv and Liebert, Tripp Lite, Mitsubishi, Toshiba, Delta, XPC and others. GDF is a certified partner of XPC and Delta.

Sizes

Work in GDF’s records runs from single-phase rack and tower units under 3 kVA to three-phase systems of 800 kVA and above.

Response

24/7 line at 514-252-8324. Rapid dispatch: 1 to 3 h in the Montreal area, same day in Quebec City, Toronto and Ottawa; 24 to 48 hours elsewhere in Canada.

Quote

A written quote within 4 business hours once we have the model, the rating and the symptom.

Report

A written report after each visit: readings per unit, photos, findings and numbered recommendations, with a green, yellow or red status.

Warranty

Extended warranties on parts and labour are available on request.

What breaks in a UPS, and how is it repaired?

UPS repair for APC, Eaton, Tripp Lite and Liebert UPS: what fails most, how we find the real cause behind an alarm, and when repair stops making sense. GDF Technologies repairs UPS across Canada: large and three-phase units on site, smaller rack and tower units on our bench in Montreal.

Chapters: 0:00 Intro · 0:14 Why it matters · 0:35 1. What fails most · 1:04 2. On site or on our bench · 1:32 3. Finding the real cause · 2:18 4. When repair stops making sense · 2:58 5. What to send us · 3:12 Recap · 3:34 Takeaway and our services

Chapters and transcript

Intro

Your UPS won’t turn on, it shuts itself off, or it keeps failing its self-test. This is how we find what failed in APC, Eaton, Tripp Lite and Liebert UPS, and how we fix it. And when repair stops making sense, we tell you.

Why it matters

At a group of municipal buildings in the Montreal region, a UPS kept failing its self-test. The batteries were worn out. But an internal communication fault was failing the test too. And the power strips in the rack were overloaded, with their connectors running hot. New batteries alone would not have cleared it. Here’s how we find the real cause.

One. What fails most

One: what fails most. Batteries, by far: worn-out batteries show up in about a third of our service reports. Next come the parts that wear with time: fans, capacitors, and the power boards and modules. Heat and dust wear all of them faster. At a cement plant, a Liebert NX and a Toshiba UPS needed dust cleaning and a new fan bearing. And communication: a network card or firmware fault can make a working UPS look like a failed one.

Two. On site or on our bench

Two: on site or on our bench. Large and three-phase UPS are repaired where they stand, with your equipment on the maintenance bypass while we work. Smaller rack and tower units can come to our bench in Montreal, where we test them under a real load. On one bench test, two small custom-built 1 kVA online UPS carried 72 percent of their rating for a few seconds, then collapsed and kept cycling. Neither was fit for the job, and the bench showed it before they went into service.

Three. Finding the real cause

Three: finding the real cause. An alarm tells you where the UPS felt the problem, not always where it started. At a food plant in southern Ontario, a 300 kVA Mitsubishi had logged an inverter fault. The plant had run on bypass for two months. The first cause was a worn-out battery string dragging the DC bus down. We installed new batteries, then planned a full shutdown to test the inverter itself. Small units too: at a transportation hub, one APC Smart-UPS SRT refused its self-test with two-year-old batteries, and another showed a logic fault. We recommended replacing those two units and keeping the rest of the fleet. If your UPS went to bypass on its own, it did that to keep your equipment powered. But on bypass, nothing protects the load.

Four. When repair stops making sense

Four: when repair stops making sense. Age comes first. Small single-phase units reach the end of their life around eight to ten years. Mid-size three-phase units, around fifteen. Then parts. Tripp Lite’s SU8000 and SU10000, for example, are discontinued, and spare parts are gone. At a network operator in the Toronto area, a 24-year-old Powerware 9315 lost its capacitors. All 90 were replaced, and the static bypass had failed too. We quoted the repair, with its risks. We recommended a modular replacement with new batteries. When it’s close, you get both options in writing, so you can decide.

Five. What to send us

Five: what to send us for a fast quote. The make and model, the serial number, and a photo of the rating plate. A photo of the display with the alarm or error code, and what happened just before. And the size of the load, if you know it.

Recap

To recap. Batteries fail most, then fans, capacitors, boards and communication. Heat and dust speed all of it up. Large UPS are repaired on site. Smaller units can come to our bench. We follow the fault to its cause, not just to the alarm. When age or parts make repair a poor bet, we tell you, and you get both options in writing.

Takeaway and outro

If the alarm comes back after new batteries, something else is failing. Have the whole UPS checked. GDF Technologies repairs UPS across Canada. We offer support when you need it, and when something fails, we’re there day or night. We also offer extended warranties on parts and labour. And when it’s time for a new UPS, we do the consulting and engineering with you, from configuration to delivery and installation. Call us, or ask for a quote at gdftech.com. You’ll hear back within four business hours.

On site or bench

On site, or on our bench in Montreal

It is one of the questions customers ask most: 34 threads in GDF’s work database ask whether a unit can be diagnosed on site or brought in. The answer depends on the size of the UPS and on what it protects.

On site

Three-phase systems, battery cabinets and any UPS that protects a running load are repaired where they stand. The technician reads the event log, measures, and plans a shutdown window only when the repair needs one.

On the bench

Smaller rack and tower units can come to our bench in Montreal.

A bench result

On one bench evaluation, two custom-built 1 kVA online units collapsed within seconds under a 720 W resistive load, 72 percent of their rating, and were reported not fit for purpose. See a bench diagnosis of an XPC P91-3000.

What fails

What fails, and what we repair

Findings in 150 written GDF service reports (2016 to 2026). Most repairs start with the batteries, but the electronics wear too.

Finding in the reportShare of reports
Batteries at or past end of life35%
Room too hot, poor ventilation or contamination24%
Acid leak, corrosion or sulphation on blocks or terminals23%
UPS discontinued, past service life, parts scarce15%
UPS shut down, would not start or dropped the load13%
Battery alarm or failed self-test11%
UPS transferred to, or stuck on, bypass9%
Failed or noisy fans6%
Power module, board, SCR/IGBT or inverter fault5%
AC or DC capacitors aged or failed3%

Some parts wear by design. Eaton advises treating capacitors as the perishable commodity they are and replacing them at or near the end of their rated service life. On Schneider Electric’s Symmetra PX 250/500, the power-module life-cycle alarm means the modules are at end of life because of wearing components such as fans, capacitors and power supplies, even while they still run. Capacitor, fan, module and board parts appear in 137 of GDF’s 761 quotes.

It matters beyond the UPS itself. In Uptime Institute’s 2026 analysis, power-related issues caused more than one in five IT service outages reported over three years, and among those power causes, UPS failures remain the most frequently cited, followed by transfer switch and generator issues.

How it runs

How a repair call runs

  1. Send the details. Model and serial number, the rating in kVA, photos of the display and the nameplate, the alarm or error shown, and the age of the batteries if you know it.
  2. Safe checks while you wait. For an APC Smart-UPS SMT that will not turn on, Schneider Electric’s checklist starts with the basics: the unit switched on, the power cable, the input breaker and the battery connector. If the UPS reports an internal fault, stop using it and have it serviced. Do not open the unit: before any battery work, the battery breaker and the DC strings are isolated.
  3. Diagnosis. The technician reads the display and the event log (outages, transfers, faults, last self-test), measures input and output per phase and the load, inspects fans, filters, connectors and capacitors, and checks each battery block, internal resistance included.
  4. Repair. Batteries, fans, capacitors, fuses, boards or power modules, or the bypass path. Work that needs the load on maintenance bypass is planned with you: in bypass the load is unprotected, so online work is preferred for critical loads.
  5. Back online, with a report. The UPS goes back to normal with no active alarm, and you receive the written report with readings, photos and the next steps.
Repair or replace

Repair or replace?

A repair makes sense while parts exist and the frame is not at the end of its life. In GDF reports, small single-phase units are treated as end of life around 8 to 10 years, mid-size three-phase units (the Eaton 9155 class) around 15 years, and large Toshiba or Mitsubishi frames up to 20 years with capacitor and fan renewals.

Three more checks: whether parts are still available (15% of reports found a discontinued UPS or scarce parts), the state of the batteries, and the load. The median UPS in GDF reports runs at about 25 percent of its rating, which favours a smaller or modular unit when the time comes to replace.

For the full decision, with end-of-support dates by maker, read repair or replace an ageing UPS.

From the field

Repairs from the field

300 kVA, 24 years old

A Powerware 9315 at a network operator in the Toronto area was called in after a capacitor failure. All 90 capacitors were replaced with the OEM kit, but the static bypass SCRs were cracked or shorted and the bypass fuse blown, so the load sat unprotected on the external maintenance bypass. A repair was quoted with its risks; the recommendation was a modular replacement with new batteries.

Two months on static bypass

At a food plant in southern Ontario, a 300 kVA Mitsubishi 9900B had run on static bypass since an inverter overcurrent code. The cause was an end-of-life battery string dragging the DC bus: 80 new blocks went in, and a cold restart was planned in a shutdown window to diagnose the inverter.

A fleet of 11 Smart-UPS SRT

At a transportation hub, the batteries were only 2 years old, yet one unit refused its self-test and showed a runtime of 1 h 30 that could not be trusted, and another showed a logic anomaly. The recommendation: replace the two faulty units, fix the ventilation and put the fleet on annual follow-up.

FAQ

Questions about UPS repair

Can you diagnose the UPS on site, or can we bring it to you?

Both. Three-phase systems and units that protect running loads are diagnosed on site. Smaller rack and tower units can come to our bench in Montreal.

What do you need to prepare a repair quote?

The model and serial number, the rating in kVA, photos of the display and the nameplate, the alarm or error shown, and the battery age if you know it. You receive a written quote within 4 business hours.

We replaced the batteries and the alarm is still there. What else could be wrong?

Common causes: the new batteries are not connected securely, the alarm and service counters were not reset after the swap, or the fault lies elsewhere. On one GDF site, self-test failures were traced to an internal communication fault.

My UPS will not turn on. What should I check first?

For a plug-in unit such as an APC Smart-UPS SMT, Schneider Electric’s checklist: the unit switched on, the power cable connected, the input breaker not tripped and the battery connector secure. If the display reports an internal fault, do not use the UPS: unplug it and have it serviced. For a three-phase system, call the 24/7 line.

Is my old UPS worth repairing?

Often, if parts are available and the frame is within its life: about 8 to 10 years for small single-phase units, around 15 for mid-size three-phase units, up to 20 for large frames with capacitor and fan renewals. Past that, plan the replacement.

Which UPS brands do you repair?

APC and Schneider Electric, Eaton and Powerware, Vertiv and Liebert, Tripp Lite, Mitsubishi, Toshiba, Delta, XPC and others. GDF is a certified partner of XPC and Delta.

How fast can a technician come?

The line is open 24/7 at 514-252-8324. Rapid dispatch: a technician is on site within 1 to 3 h in the Montreal area, the same day in Quebec City, Toronto and Ottawa, and within 24 to 48 hours elsewhere in Canada.

Need a UPS repaired?

Send the model, the rating and the alarm on the display. You receive a written quote within 4 business hours.