Skip to main content

APC UPS error codes and audible alarms: complete troubleshooting guide

What F01 to F09, L.01 and L.02, the text alarms and the LED patterns actually mean on each APC family, taken from Schneider Electric’s own troubleshooting documents, with the correct next step for each. If your UPS is in alarm right now, GDF Technologies provides 24/7 emergency UPS service across Canada.

Request emergency service
Or call our 24/7 line: (514) 252-8324

Quick answer: On an APC Back-UPS Pro or Back-UPS RS with an LCD, F02 means “On-Battery Output Short”: something plugged into the battery outlets is shorted. Turn the UPS off, unplug everything from the battery outlets, turn it back on, then reconnect one item at a time. F01 is an on-battery overload you can clear by shedding load. F03 to F09 (including F05, the charger fault) cannot be corrected by the user. On a Smart-UPS C, L.01 means the battery is near end of life and L.02 means it has passed it. Smart-UPS SMT, SMX and SRT units show text messages, not F codes: a Fault LED there means note the LCD message, move critical load to another source, then contact support.

An APC UPS reports trouble in four different ways depending on the family: a two-digit F code on the small LCD of a Back-UPS Pro, a P, b, G or L code on a Smart-UPS C, a plain text message on a Smart-UPS SMT, SMX or SRT, or an LED pattern and tone on the compact Back-UPS ES. The same symptom means different things across these families. The most common error is reading F02 as a charger fault: on the units that display it, APC defines F02 as an output short, and the charger fault is F05.

The meanings and actions below come from Schneider Electric’s published troubleshooting documents for each family, plus the Canadian voltage standard where it matters. Where our own field guidance is added, it is labelled as such, and where the documents cited here give no meaning for a code, we say so rather than guess. If the unit is beeping and you want the tone decoded first, the audible patterns are covered in detail in what each APC UPS beep pattern means.

Video: APC UPS error codes and what to do (3 minutes)

In this video:

  • 0:00 APC UPS error codes
  • 0:16 The four code families
  • 0:53 The fixes that are yours
  • 1:30 When the manual says call
  • 2:15 Diagnose across Canada
Transcript

An APC UPS shows a code on its display, like P00 or b02. The letter is the family, and the family tells you whether the fix is yours or a technician's. Here is the Smart-UPS C list, family by family, from its own manual.

The code families. P codes are power and output events: P00 is an output overload, P01 a short circuit on the output, P13 an inverter error. b codes are battery events: b00, battery disconnected, b02, battery needs replacement, b03, battery overtemperature. G codes are general and system events, from the wiring code G00 to G08, a firmware mismatch. And L codes are battery lifetime: L01, lifetime near end, L02, lifetime exceeded.

Most of that list is a call for service, and the manual says so. But four messages are yours to handle. The L codes: press mute, and the alarm acknowledges. The weak charge message: recharge for at least four hours, run a self-test, and replace the battery only if the problem persists. A Replace Battery icon flashing with a beep every 2 seconds: the replacement battery is not properly connected, so reconnect the battery connector. And on a Back-UPS Pro, F01, the on-battery overload: turn it off, disconnect the non-essential equipment from the battery backup outlets, and turn it back on.

Everything else in those tables is a technician's. On the Back-UPS Pro, F02, the output short, has one user step, disconnect everything and reconnect one item at a time to find the device that trips it, but the manual sends F04 through F09, clamp short, charge error, relay welding, temperature, fan and internal error, straight to Schneider Electric support. On the Smart-UPS side, the internal G family, the memory, communication and subsystem codes, is factory territory. And G00 is not the UPS at all: a site wiring error means missing ground, reversed polarity or an overloaded neutral, and a qualified electrician inspects the building wiring.

If your code is not on this list, or it comes back after the fix, stop resetting and get it diagnosed. GDF Technologies diagnoses APC UPS errors across Canada, around the clock: same-day response in Montreal, Quebec City, Toronto and Ottawa, and 24 to 48 hours elsewhere. Note the code and the model, and call 514-252-8324.

Scope and how to use this guide

This page covers single-phase APC by Schneider Electric UPS units sold in Canada at 120 V: Back-UPS ES (BE, BN), Back-UPS Pro and Back-UPS RS (BR, BN, BX models with an LCD), Smart-UPS C (SMC), Smart-UPS line-interactive (SMT, SMX) and Smart-UPS On-Line (SRT). It explains what the unit is reporting, which actions APC documents as safe for the user, and which conditions need a technician.

Out of scope: the internal repair of any unit, firmware-specific behaviour not documented by APC, and three-phase Symmetra and Galaxy systems, which report text alarms through their own displays and network cards and are covered only in the safety section. We do not publish runtime figures here; runtime depends on the load and battery age and is better estimated with the UPS runtime calculator.

Three assumptions apply throughout. The UPS has a 120 V input. The battery is the original type or a correct replacement cartridge. Nobody has opened the chassis. If any of these is not true, start with the safety section. If the unit is still under manufacturer warranty, contact APC first: third-party repair may affect warranty coverage.

1. Identify how your APC reports faults

Read the full model number on the rear label before looking anything up. It tells you which of the four reporting systems you are dealing with (the prefix alone is not enough: BN is used for both Back-UPS ES and Back-UPS Pro models), and therefore which table on this page applies. Table 1 maps each family to its fault display, using the model lists that APC gives in each troubleshooting document.

Table 1. How each APC single-phase family reports a fault. Source: Schneider Electric FAQs FA279106, FAQ000264323, FA310801, FA279118, FAQ000260345, FA299165, FA279109, FA279125 and FA310519.
Family Example models What you see on a fault Table to use
Back-UPS Pro / Back-UPS RS with LCD BR1300G, BR1500G, BR1000MS, BR1500MS2, BN1350M2, BN1500M2, BX1500M SYSTEM FAULT indicator plus a code F01 to F09 on the LCD Table 2
Smart-UPS C SMC1000, SMC1500, SMC1500-2UC Fault or Replace Battery LED; battery alarms L.01 / L.02 on the LCD Table 3
Smart-UPS line-interactive SMT2000, SMT3000, SMX1500RM2U Fault LED plus a text message on the LCD, no numeric F code Table 4
Smart-UPS On-Line SRT3KXLT, SRT3KRMXLT Red (internal alert) or amber (overload) display backlight plus a text message Table 4
Back-UPS ES (no LCD) BE600M1, BN650M1, BN650M1-CA, BN675M1 Power button colour and flash rate, a Building Wiring Fault LED, and tones Table 5
Figure 1. Routing an APC UPS alarm to the right table Decision diagram. Start with what the UPS shows. An F followed by two digits on the LCD leads to the Back-UPS Pro and RS table. L.01 or L.02 leads to the Smart-UPS C section. A text message on the LCD leads to the Smart-UPS SMT, SMX and SRT section. LEDs only with no display leads to the Back-UPS ES section. A building wiring fault indicator leads to a qualified electrician. A tone with no other indication leads to the beep table. What does the UPS show? Read the display first, then the LEDs F + 2 digitson the LCDe.g. F02 L.01 or L.02on the LCDSMC units Text messageon the LCDSMT, SMX, SRT LEDs onlyno displayBE, BN ES Building wiringfault indicatorlit or shown Tone onlynothing elsecount the beeps Table 2Back-UPS Pro, RS Table 3Smart-UPS C Table 4Smart-UPS text Table 5Back-UPS ES Stopcall an electrician Table 6beep patterns A three-phase Symmetra or Galaxy in alarm is always a technician call: see the safety section. Routing drawn by GDF Technologies from the family definitions in Schneider Electric’s troubleshooting FAQs.
Figure 1. Start from what the unit actually displays, not from the symptom. Each branch points to the table on this page that applies to that family. The building wiring branch stops at an electrician: APC’s Back-UPS documents say not to operate the UPS on a faulted outlet, and its Smart-UPS documents call for an electrician’s inspection.

2. Back-UPS Pro and Back-UPS RS F codes (F01 to F09)

The numeric F codes belong to the Back-UPS Pro and Back-UPS RS units that have a small LCD. When one appears, the SYSTEM FAULT indicator lights and APC’s instruction is to match the number on the LCD to its code list. APC publishes the list in three troubleshooting documents for these ranges (BR1300G / BR1500G, the BR and BN “MS/MS2/M2” models, and the BX850M to BX1500M). The lists match except for three points: F08 (Fan Fault) appears only in the BR1300G / BR1500G document, F05 is called “Charger Fault” there and “Charge Error” in the other two, and F09 is “Internal Fault” there and “Internal Error” in the other two.

Table 2. Back-UPS Pro and Back-UPS RS system fault codes as published by Schneider Electric, with APC’s corrective action. Sources: code names from FA279106 (BR1300G, BR1500G), FAQ000264323 (BR 1000/1350/1500 MS/MS2, BN 1100 to 1500 M2 and M2-CA) and FA310801 (BX850M to BX1500M); corrective actions from FAQ000264323 and FA310801. FA279106 itself says to contact technical support when the system fault indicator is lit.
Code APC meaning Can the user clear it? APC’s corrective action
F01 On-Battery Overload Yes Turn the Back-UPS off, disconnect non-essential equipment from the Battery Backup outlets, turn it back on.
F02 On-Battery Output Short Yes, if the short is in the connected equipment Turn the Back-UPS off, disconnect all equipment from the Battery Backup outlets, turn it on, then reconnect equipment one item at a time.
F03 On-Battery Xcap Overload No Contact technical support.
F04 Clamp Short No Contact technical support.
F05 Charger Fault / Charge Error No Contact technical support.
F06 Relay Welding No Contact technical support.
F07 Temperature No Contact technical support.
F08 Fan Fault (listed for BR1300G / BR1500G) No Contact technical support.
F09 Internal Fault / Internal Error No Contact technical support.

For the last seven rows, the BR/BN and BX documents are explicit: errors F03 to F09 cannot be corrected by the user. That gives a simple triage rule. F01 and F02 are about what is plugged in, so they are worth one careful attempt at the outlets. Every other F code is about the UPS itself.

3. F02 on an APC UPS: on-battery output short

F02 is the code most people search for, and it is widely misreported as a charger fault. On the Back-UPS Pro and RS units that display it, APC defines F02 as On-Battery Output Short: a short circuit on the battery-backed outlets while the unit is running on battery. In our field experience the culprit is usually a connected device, cord or power bar, not the battery; APC’s own corrective action points the same way, since it starts by disconnecting the equipment.

APC documents a second situation that produces the same display. Schneider Electric’s FAQ on F02 and F04 at power-on (models BX1500M, BN1350M2 and BN1500M2) says that if the internal battery has not been correctly connected, the unit may show F02 or F04 when it is switched on. APC documents that case for those three models; the battery connector check below is harmless on other Back-UPS Pro units, but the diagnosis is only documented for them.

Figure 2. APC F02 isolation sequence Flow chart. Step 1: turn the UPS off and disconnect all equipment from the battery backup outlets. Step 2: turn the UPS on with nothing connected. If F02 is gone, reconnect equipment one item at a time; the item that brings F02 back has the short and stays off the UPS. If F02 is still shown, check that the battery connector is firmly seated, then unplug the UPS from the wall and try switching it on from the battery alone. If F02 persists, stop using the UPS and contact support or a technician with the model, serial number and a video of the display at start-up. 1. Turn the UPS off Unplug ALL equipment from battery outlets 2. Turn it on with nothing connected F02 stilldisplayed? No: reconnect one itemat a time, restarting each time The item that brings F02back has the short.Keep it off the UPS. Yes: check the batteryconnector is firmly seated Unplug from the wall,switch on from battery only Still F02: stop using it.Contact support or a technicianwith model, serial, video Steps from Schneider Electric FAQ000264323 and FA310801 (output short) and FAQ000273815 (battery connection at power-on, BX1500M, BN1350M2, BN1500M2).
Figure 2. The F02 sequence combines APC’s two published instructions: isolate the connected equipment first, because an output short is the documented meaning, then rule out a badly seated battery connector, which APC lists as a cause of F02 or F04 at power-on.

What to do with F02, in order

  1. Turn the UPS off. Disconnect every device from the Battery Backup outlets; the surge-only outlets are not involved.
  2. Turn the UPS on with nothing connected. If the code does not return, turn the UPS off, plug in one device, turn the UPS back on, and repeat for each device. The device whose connection brings F02 back, or its cord or power bar, has the short. Keep it off the UPS until it has been checked.
  3. If F02 appears with nothing connected, check that the internal battery connector is pushed fully home. This is APC’s first step in its power-on F02 / F04 FAQ.
  4. Following the same FAQ, turn the UPS off, unplug it from the wall and try switching it on again from the battery alone.
  5. If the unit still shows F02, stop. APC’s instruction at that point is to contact support with the model number, the serial number and a video of the display during start-up. Do not keep a UPS that shows an output short at start-up in front of equipment you care about.
GDF field note: a user who believes F02 is a charger fault will often buy a new battery or a new UPS, then plug the same faulty power bar or device back in and get F02 again. Isolating the connected equipment costs nothing and is APC’s documented first step. If a replacement cartridge is needed later for a BR1300G or BR1500G, APC names the APCRBC124 cartridge in its FAQ; a replacement battery compatible with the APCRBC124 cartridge (not an APC-made part) ships from Montreal.

4. F01, F05 and the codes you cannot clear

F01, On-Battery Overload. The load on the battery outlets exceeded what the UPS can carry on battery. APC’s action is to turn the unit off, move non-essential equipment off the Battery Backup outlets, and turn it back on. In our experience, laser printers, space heaters and power bars daisy-chained into the battery outlets are frequent causes. If F01 returns with a modest load, compare the load with the unit’s rating; it may simply be under-sized for the job.

F05, Charger Fault or Charge Error. This, not F02, is the code APC names as a charging fault, and APC classes it as one the user cannot correct. Contact support before buying a battery: a new battery is not a documented fix for F05.

F03, F04, F06, F07, F08 and F09. Xcap overload, clamp short, relay welding, temperature, fan fault and internal fault all describe the condition of the UPS itself. APC’s position is the same for all of them: contact technical support. Two GDF field notes follow from that. First, with F07 (temperature) it is worth checking the room before calling: a unit pushed against a wall or buried in a closed cabinet may simply be hot. Second, F06 indicates a welded relay and APC gives no user action for it, so take the unit out of service rather than restarting it repeatedly.

For a Back-UPS Pro, the repair-or-replace decision after an internal code is usually an economic one. For a Smart-UPS or anything protecting regulated equipment, a documented assessment is the better route; our APC UPS maintenance and repair service covers both.

5. Smart-UPS C: what L.01 and L.02 mean

On Smart-UPS C models (SMC), the codes L.01 and L.02 are battery end-of-life alarms, not communication faults. Schneider Electric’s FAQ for all SMC models states that L.01 means the battery is near end of life and L.02 means it has exceeded end of life. APC’s instruction for both codes is to acknowledge the alarm with a short press of MUTE (about 0.2 second) and contact technical support to arrange the battery replacement as soon as possible.

Table 3. Smart-UPS C battery and fault indications. Sources: Schneider Electric FAQ000260345 (L.01, L.02, all SMC models) and FA279118 (SMC1000 / SMC1500 troubleshooting).
Indication APC meaning Next step
L.01 Battery is near end of life Short press on MUTE, arrange the battery replacement as soon as possible.
L.02 Battery has exceeded end of life Short press on MUTE, arrange the battery replacement as soon as possible.
Replace Battery LED Weak charge, or battery connector not secure Recharge at least 4 hours, run a self-test, check the connector; replace if it persists.
Fault LED Possible internal fault Contact APC support.
Site wiring fault message Building wiring problem detected (120 V units) Have a qualified electrician inspect the building wiring.

If an SMC shows a code that is not in this table, the FAQs cited here do not define it, so we do not publish a meaning. Note the exact code, the model and the serial number before calling support; that is what any technician will ask for first. In a clinic or other regulated site, have the replacement done and logged by qualified staff or your service provider, then run a self-test.

6. Smart-UPS SMT, SMX and SRT: text alarms, not F codes

Code lists that attribute numeric F codes to the Smart-UPS SMT and SRT families, including an earlier version of this page, do not match the APC troubleshooting documents cited here: those documents describe faults as messages on the LCD, not numeric F codes. An SMT, SMX or SRT lights its Fault LED or changes its display backlight and writes the condition in words on the LCD. When a Smart-UPS reports an internal fault, APC asks you to note the exact message on the LCD and contact support. Before switching off a unit that is carrying critical load, move that load to another source.

Table 4. What Smart-UPS SMT, SMX and SRT units report, with APC’s corrective action. Sources: Schneider Electric FA299165 (SMT2000, SMT3000 and RM2U versions), FA279109 (SMX1500RM2U) and FA279125 (SRT3KXLT, SRT3KRMXLT).
What you see APC meaning APC’s action
Fault LED with an LCD message Possible internal fault Note the exact message, contact support. GDF note: move critical load to another source before shutting the unit down.
Replace Battery LED or “Replace Battery” Battery weak, near end of service life, or not properly connected Recharge at least 4 hours, run a self-test, secure the connector, replace if it persists.
“Disconnected Battery” (SRT) Battery cables disconnected Secure the cables, run a self-test from the Test and Diagnostics menu.
Overload with an audible alarm Connected equipment exceeds the rating Disconnect non-essential equipment.
Bypass mode (SRT) UPS has transferred to bypass No action if intentional; if automatic, read the accompanying alert.
Red backlight (SRT) Internal UPS alert or warning Do not attempt to use the UPS; turn it off and have it serviced (move critical load first).
Amber backlight (SRT) Overload condition Reduce the load; disconnect non-essential equipment.
Display LEDs flash in sequence Shut down remotely by software None; it restarts when utility power returns.
Site wiring fault message Missing ground, reversed polarity or similar (120 V units) Have a qualified electrician inspect the building wiring.

If a Smart-UPS is running on battery while it is plugged in, APC points first at a tripped input breaker or at input voltage that is too high, too low or distorted, and suggests testing the outlet and trying another circuit.

7. Back-UPS ES: reading the LED patterns

The compact Back-UPS ES units have no display. The power button changes colour and flash rate, and a separate indicator lights for building wiring faults. The patterns below are APC’s own definitions for the BE600M1 and BN650M1 family; other Back-UPS ES models use similar but not identical patterns, so check the FAQ for your exact model.

Table 5. Back-UPS ES indicator patterns and APC’s actions for BE600M1, BN650M1, BN650M1-CA and BN675M1. Source: Schneider Electric FA310519.
Indication APC meaning Action
Green button flashes twice every 2 seconds Operating on battery power Save files and shut down; the battery recharges when power returns.
Green button flashes rapidly About two minutes of runtime left Save work and shut down now.
Button alternates green and red with a constant tone Battery disconnected or near end of life Reconnect the battery, or replace it (APC names APCRBC154).
Building Wiring Fault LED lit Building wiring presents a shock hazard Do not operate the UPS; call a qualified electrician.
Beeps twice every 30 s (Quiet Alarm) or once every 4 s (Full Alarm) while the outlets are off Input voltage too low to start but high enough to charge Use Quick Mute; it normalises when voltage recovers.
Power button alternates green and amber Short circuit or fault detected on a USB charging port Disconnect the USB device; charging resumes when the button turns solid green.

8. What the tone adds to the diagnosis

The beeps confirm the operating state but rarely identify a fault on their own. Schneider Electric publishes the same core patterns for Back-UPS and Smart-UPS. Use them with the display or LEDs, not instead of them.

Table 6. APC audible alarm patterns. Sources: Schneider Electric FA158827 (Back-UPS) and FA156554 (Smart-UPS audible alarms).
Pattern Meaning Action
4 beeps every 30 seconds, or 1 beep every 5 seconds On battery Normal during an outage; if frequent, check the input voltage.
Continuous beeping Low battery; about 2 minutes left on a Back-UPS (on a Smart-UPS the warning time defaults to 2 minutes and is configurable) Shut the operating system down gracefully now.
Constant solid tone Overload Remove non-essential equipment.
Continuous beeps for 1 minute, repeated every 5 hours Failed self-test Check the battery connection and load, re-run the self-test, plan a battery replacement.
Chirp every 4 seconds with Replace Battery LED flashing (Smart-UPS) Battery disconnected Reconnect the battery.

The full audible guide, with the triage sequence and the difference between the four patterns in the first minute, is on our page explaining why an APC battery backup keeps beeping.

9. Site wiring faults and Canadian power conditions

A site wiring or building wiring fault is not a UPS failure. It means the UPS has detected a problem with the receptacle it is plugged into. Schneider Electric’s FAQ on the indicator lists the three conditions it detects on 120 V Back-UPS and SurgeArrest products: an overloaded neutral (more than 5 V AC measured between neutral and ground), reversed polarity (hot and neutral swapped), and a missing ground, including the use of a three-prong to two-prong adapter. APC’s instruction is to have a qualified electrician inspect the wiring and to use the UPS only on a properly grounded outlet where the indicator stays off; for the Back-UPS ES family it states plainly not to operate the UPS while the indicator is lit.

A second Canadian reality produces many “on battery while plugged in” calls. The reference for supply voltage in Canada is CSA CAN3-C235-83, which sets the normal and extreme variation limits at the service entrance. A line-interactive UPS corrects moderate deviations with its automatic voltage regulator and transfers to battery beyond its configured transfer points; APC’s Back-UPS documents list input voltage out of range as a cause of running on battery while plugged in.

Table 7. Voltage variation limits at the service entrance for 120 V and 120/208 V systems under CSA CAN3-C235-83, Table 3, as reproduced in a Canadian distributor’s conditions of service (Newmarket-Tay Power Distribution, COS-230-05).
Nominal system Extreme low Normal low Normal high Extreme high
120/240 V single-phase 106/212 V 110/220 V 125/250 V 127/254 V
120/208 V three-phase, 4-wire 110/190 V 112/194 V 125/216 V 127/220 V

Two practical consequences follow. A UPS that switches to battery repeatedly at a site whose measured voltage sits inside the normal band is more likely set to high sensitivity, or on a circuit with a local problem, than suffering a utility fault; APC’s Back-UPS Pro troubleshooting advice is to adjust the transfer voltage and sensitivity range, and its Smart-UPS advice is to test the outlet and try another circuit. On generator power, which is common at remote and industrial sites across Canada, APC notes that frequency deviations beyond about ±5% put a Back-UPS on battery, and that a generator should be three to five times the size of the total load to hold frequency steady.

10. Symmetra, Galaxy and the safety limits of self-diagnosis

Modular and three-phase systems (Symmetra LX and PX, Galaxy 3500, Galaxy VS, VM and VX) report alarms as text on their own displays and through the network management card event log, and their meaning depends on the module and firmware. We do not publish a code table for them here: the troubleshooting FAQs this guide relies on do not cover them, the alarm lists sit in each system’s own manuals, and the first action for any alarm on these systems is the same: a qualified technician with the event log. For a Symmetra or Galaxy in alarm, call our APC service team rather than acting on a generic list.

Do not open the chassis. A UPS battery string stores energy whether or not the unit is plugged in, and larger systems carry DC buses at hundreds of volts. APC’s instructions for F03 to F09 and for Smart-UPS internal faults stop at “contact support”, and that is where user work should stop too. Reseating a user-replaceable cartridge following the manufacturer’s procedure is the limit of safe user work.

Call a technician whenever any of the following is true:

  • A Back-UPS Pro or RS shows F03 to F09, or F02 persists with nothing connected.
  • A Smart-UPS lights its Fault LED or shows a red backlight with an internal fault message.
  • Any Symmetra or Galaxy is in alarm, or any UPS has transferred to bypass on its own and will not return.
  • The UPS protects equipment in a hospital, data centre, telecom room or other regulated environment, whatever the code.
  • A building wiring fault is shown: that call goes to a licensed electrician first.

For battery-related alarms on critical systems, our UPS battery replacement service handles the replacement, the runtime check and the disposal record, and our preventive maintenance programs catch end-of-life alarms before they turn into dropped loads.

11. Decision checklist and records to keep

Use this sequence the moment an APC UPS alarms:

  1. Is the load still powered? If not, and the load is critical, move it to another source before diagnosing.
  2. Read the model prefix and what the unit shows (Figure 1). Pick the matching table.
  3. Is it a building wiring fault? Stop and call an electrician.
  4. Is it F01, F02 or an overload message? Isolate the connected equipment (Figure 2).
  5. Is it a battery alarm (L.01, L.02, Replace Battery)? Recharge, self-test, then arrange the replacement. Check the battery’s age against the expected UPS battery service life, and find the right cartridge in the APC RBC cross-reference.
  6. Is it anything else (F03 to F09, internal fault, red backlight)? Take the unit out of service and call support or a technician.

Keep a short record for every alarm; a regulated site will be asked for it:

  • Date and time, model and serial number, and the exact code or message as displayed (a phone video of start-up is what APC asks for).
  • What was connected to the battery outlets and what was disconnected to clear the alarm.
  • Battery installation date, last self-test result and any runtime test result.
  • Measured receptacle voltage if the unit was running on battery while plugged in, and the sensitivity setting in use.
  • Who was called, what was replaced, and the date the unit returned to service.

Other manufacturers use different conventions; if the site also runs Eaton equipment, the equivalent reference is our Eaton UPS alarm and fault code guide.

12. Sources

All Schneider Electric documents were read on 22 September 2026. Where two documents word a code differently, both wordings are shown in the tables. APC, Back-UPS, Smart-UPS, Symmetra and Galaxy are trademarks of Schneider Electric. GDF Technologies is an independent UPS service company and is not affiliated with or endorsed by Schneider Electric.

  1. Schneider Electric, FA279106, basic troubleshooting steps for the Back-UPS RS BR1300G / BR1500G (system fault codes F01 to F09; APCRBC124).
  2. Schneider Electric, FAQ000264323, basic troubleshooting steps for the Back-UPS Pro BR/BN MS, MS2, M2 and M2-CA models (F01, F02 actions; F03 to F09 not user-correctable).
  3. Schneider Electric, FA310801, basic troubleshooting steps for the Back-UPS Pro BX850M to BX1500M.
  4. Schneider Electric, FAQ000273815, F02 or F04 error code when turning on Back-UPS (battery connection at power-on).
  5. Schneider Electric, FAQ000260345, SMC L.01 or L.02 battery end of life alarm.
  6. Schneider Electric, FA279118, basic troubleshooting steps for the Smart-UPS SMC1000 / SMC1500.
  7. Schneider Electric, FA299165, basic troubleshooting steps for the Smart-UPS SMT2000 / SMT3000 and RM2U models.
  8. Schneider Electric, FA279109, basic troubleshooting steps for the Smart-UPS SMX1500RM2U.
  9. Schneider Electric, FA279125, basic troubleshooting steps for the Smart-UPS SRT3KXLT / SRT3KRMXLT.
  10. Schneider Electric, FA310519, basic troubleshooting steps for the Back-UPS ES BE600M1 and BN650M1 family.
  11. Schneider Electric, FA158817, what the Site Wiring Fault indicator represents.
  12. Schneider Electric, FA158827, why an APC Back-UPS might be beeping (alarm patterns, generator frequency note).
  13. Schneider Electric, FA156554, descriptions of Smart-UPS audible alarms.
  14. CSA Group, CAN3-C235-83, Preferred voltage levels for AC systems, 0 to 50 000 V, Table 3, as reproduced in Newmarket-Tay Power Distribution, Conditions of Service COS-230-05, Voltage Guidelines.

24/7 emergency APC UPS service across Canada

GDF Technologies provides on-site diagnosis, repair and battery replacement for APC UPS systems across Canada, from Back-UPS Pro units in branch offices to Symmetra and Galaxy systems in data centres and hospitals. Send us the model, serial number and the code or message on the display, and we will tell you whether it is a user fix, a battery or a service call.

Request emergency service
APC services overview

24/7 emergency line: (514) 252-8324

Close Menu