Short answer: a UPS diagram is read as an energy path between six blocks: rectifier-charger, DC bus and batteries, inverter, static bypass, maintenance bypass, and control and monitoring. There are three common topologies, standby, line-interactive and online double conversion, plus hybrid conversion at small ratings. Only online units feed the load through the inverter in normal mode, with no transfer (0 ms) when utility power fails, unless they are set to eco mode.
In Canada? GDF Technologies provides 24/7 UPS service across Canada, same day in Montreal, Quebec City, Toronto and Ottawa. Call 514-252-8324 or request service; we respond within 4 business hours. See our UPS services page.
Updated October 23, 2026. Written by Christian Barkley, Director, GDF Technologies, Montreal.
This guide is for engineers, technicians and facility managers who need to read a UPS diagram, whether it sits in a manual, on an electrical-room one-line drawing or on the unit’s display. It explains what each block does, where current flows in each operating mode, and what the IEC 62040-3 classification says about each diagram. The practical conclusion: to know whether a load is really protected, you need to know which path is feeding it right now, not only which unit is installed.
Scope, terms and assumptions
The guide covers static UPS units, meaning units with no rotating parts, single-phase and three-phase, from a few hundred VA to about 1,500 kVA. Rotary UPS systems (motor-generator sets, flywheels) follow a different standard and are excluded [1]. The diagrams below are block diagrams we drew: they show functions, not the wiring of a specific model. For field work, the manufacturer’s manual and the site one-line drawing govern.
One word causes most of the confusion. “Inverter” can mean the whole backup unit (in French, “onduleur” is used for the complete UPS) or the internal converter that turns DC back into AC. In this guide, “UPS” means the complete unit and “inverter” means the internal DC-to-AC converter. For the full distinction, see our article on the difference between an inverter and a UPS.
| Block | Role | What maintenance checks |
|---|---|---|
| Rectifier-charger | Converts utility AC to DC, feeds the DC bus and recharges the batteries | Charge voltage and current, charger alarms, heat |
| DC bus and batteries | Store the energy that takes over when utility power is lost | String and block voltages, temperature, runtime test |
| Inverter | Rebuilds an AC voltage from DC | Waveform, output voltage and frequency, response to a load step |
| Static bypass | Electronic switch that connects the load to utility power without conversion | Automatic transfer and retransfer, synchronization with the source |
| Maintenance bypass | Manual path that isolates the UPS for service while utility power keeps feeding the load | Switching sequence, interlocks, labelling |
| Control and monitoring | Chooses the operating mode, logs events, communicates | Event log, firmware version, remote alarms |
The general diagram: six blocks and three paths
On a double-conversion UPS, the full diagram has three paths between input and output. The main path runs through the rectifier, the DC bus and the inverter. The static bypass path connects the bypass input directly to the output through an electronic switch. The maintenance bypass path, often in a separate cabinet, goes around the whole unit through a manual switch. The batteries connect to the DC bus, usually through a dedicated breaker or disconnect.
Figure 1 shows these three paths. Standby and line-interactive diagrams are simplified versions of the same drawing, as shown further down.
Three notes for reading this drawing on a real site. First, the bypass input may come from the same source as the rectifier input or from a separate source; the site one-line drawing tells you which. Second, small units under a few kVA often have no maintenance bypass: you simply unplug the unit. Third, the batteries remain an energy source even when the input is off. Even the manual for APC’s Back-UPS Pro, a consumer unit, states it plainly: the UPS contains an internal battery and may present a shock hazard even when disconnected from the branch circuit [6].
Diagram 1: the standby UPS
In a standby UPS, the load runs directly on utility power through a filter and surge suppressor, and a transfer switch moves it to the inverter only when utility power fails. The inverter starts only at the moment of the outage, hence the name “standby”. The charger recharges the batteries in parallel [1].
What the diagram implies: during the transfer, the load sees a gap. Schneider Electric states that it typically takes almost 10 ms to detect the failure, move the transfer switch and start the inverter, and that this type commonly uses a square or stepped wave on battery [1]. A standby UPS regulates neither voltage nor frequency in normal operation: a sustained low voltage sends it to battery. It suits a workstation, not a critical server. Schneider places its usual range at 0.2 to 2 kVA [1].
Diagram 2: the line-interactive UPS
In a line-interactive UPS, the converter is permanently connected to the output. When utility power is normal, it runs in reverse to charge the batteries. When utility power fails, the transfer switch opens and energy flows from the batteries to the output through the same converter. Most models add a tap-changing transformer (automatic voltage regulation, or AVR) that boosts or bucks utility voltage without drawing on the batteries [1] [5].
What the diagram implies: voltage is regulated but frequency is not, and going to battery still takes up to about 10 ms [1]. On the other hand, AVR keeps the unit off battery during sustained low or high voltage within its regulation range, which spares battery life. Schneider describes line-interactive as the dominant type between 0.5 and 5 kVA, typically for a few servers and the network gear around them [1]. The choice between line-interactive and double conversion for a network room is covered in our comparison double conversion vs line-interactive UPS.
Diagram 3: online double conversion
In a double-conversion UPS, energy always goes through two conversions: the rectifier turns AC into DC and the inverter turns DC back into AC. When utility power is lost, the rectifier shuts down and the inverter draws from the batteries. Because the load path does not change, no switch operates: the transfer time is 0 ms [1]. Eaton describes the same principle: the equipment is isolated from raw utility power because energy is converted from AC to DC and back to AC [5].
What the diagram implies: output voltage and frequency are both regulated, and the power-factor-corrected rectifier draws sinusoidal current from the supply [1]. This is why double conversion is the most common type above 10 kVA [1] and the usual choice for data centres, hospitals and industry. The cost: two conversions in series produce more losses, and therefore more heat, than a direct utility path. Our page on the online double-conversion UPS covers the applications.
A newer variant, hybrid conversion, merges the rectifier and inverter into one converter. It regulates voltage but not frequency, with a 0 ms transfer, and Schneider places it at small ratings, 1 to 3 kVA, for dense edge environments [1].
Reading the IEC 62040-3 class from a diagram
IEC 62040-3 defines how to specify and test UPS performance. It applies to electronic UPS units with AC input and output up to 1,000 V and an energy store up to 1,500 V DC [2]. It summarizes output performance in three groups of characters, AAA-BB-CC [1]:
- AAA, input dependency: VFD (voltage and frequency dependent on the supply), VI (voltage independent) or VFI (voltage and frequency independent).
- BB, waveform in normal mode and then on battery: S for a low-distortion sine wave, X for medium distortion, Y for a non-sinusoidal wave (square or stepped).
- CC, dynamic performance on a mode change and then on a load step: 1 for no interruption, 2 for up to 1 ms of interruption, 3 for up to 10 ms of interruption (simplified; the standard also sets voltage-regulation criteria).
The class follows from the diagram. If the inverter is not already carrying the load and has to start, or reverse its power flow, when utility power fails, the first CC character cannot be 1. If nothing regulates frequency in normal mode, AAA cannot be VFI. Schneider also notes that nearly all UPS units of 2 kVA and above are classified SS, while many consumer units under 2 kVA are SY [1].
| Topology | Normal-mode path | Transfer to battery | Typical class | Usual range |
|---|---|---|---|---|
| Standby | Filtered utility, direct | Under 10 ms | VFD-SY-33 or VFD-SX-33 | 0.2 to 2 kVA |
| Line-interactive | Utility regulated by AVR | Under 10 ms | VI-SS-31 or VI-SX-31 | 0.5 to 5 kVA |
| Hybrid conversion, online mode | Integrated converter | 0 ms | VI-SS-11 | 1 to 3 kVA |
| Double conversion, online mode | Rectifier, DC bus, inverter | 0 ms | VFI-SS-11 | 1 to 10 kVA and 10 to 1,500 kVA |
One diagram, several modes: bypass, eco mode and battery
A double-conversion UPS is not always in double conversion. Many models offer a high-efficiency mode, often called eco mode or bypass normal mode, in which the load runs through the static bypass while the rectifier keeps the batteries charged. Applying IEC 62040-3, Schneider gives this mode the class VFD-SS-31: the load receives utility power as is, and a transfer of almost 10 ms occurs if utility power fails [1]. A variant offered on large units, power-factor-corrected bypass, keeps the inverter online and brings the transfer back to 0 ms (VFD-SS-11) [1]. Eaton’s 2009 paper describes multi-mode units that stay in a high-efficiency mode while power conditions allow, with typical transfers of 1 to 3 ms and efficiency of up to 99 percent [5]. Designs and transfer times vary by manufacturer: the model’s datasheet governs.
The same drawing explains the static bypass on a fault. If the inverter fails or the load exceeds its capacity, the controller transfers the load to the static bypass to avoid an outage. The load stays powered, but by raw utility power: it is no longer protected against a utility outage. Our guide bypass on a UPS: when it is normal and when it is critical gives the steps to follow, and our article on the static transfer switch and static bypass separates the two devices.
| Mode | Path feeding the load | Protection against a utility outage | IEC class per Schneider (White Paper 1) |
|---|---|---|---|
| Online | Rectifier, DC bus, inverter | Yes, 0 ms | VFI-SS-11 |
| Bypass normal (eco mode) | Static bypass, inverter on standby | Yes, after a transfer of almost 10 ms | VFD-SS-31 |
| Power-factor-corrected bypass | Static bypass, inverter online | Yes, 0 ms | VFD-SS-11 |
| On battery | Batteries, DC bus, inverter | Yes, until runtime ends | Not applicable |
| Static bypass on a fault | Utility through the static bypass | No | Not applicable |
| Maintenance bypass | Utility through the manual switch | No | Not applicable |
What the block diagram does not show
A block diagram does not replace the site one-line drawing. Several items that decide safety and availability do not appear on it.
- Disconnecting devices. Rectifier input breaker, bypass input breaker, output breaker, battery breaker or disconnect: their number and names change from one manufacturer to the next. The switching order comes from the manual, not from the block diagram.
- Neutral and grounding. In general, a transformerless UPS does not create a new separately derived system, while a model with an output transformer can; the manual and the site drawing say which. Our article on transformer vs transformerless three-phase UPS covers the difference.
- Redundancy. Two UPS units in parallel, or two distribution paths, add paths that a single unit’s diagram does not show. See N, N+1 and 2N UPS redundancy.
- External battery cabinets, with their own breakers, and battery monitoring instrumentation.
Canadian realities: voltages, standards and generators
Voltages. In Canada, a UPS may be fed at 120 V, 120/208 V, 120/240 V or 347/600 V. The Canadian UPS safety standard, CSA C22.2 No. 107.3, published jointly with UL 1778, covers units for distribution systems up to 600 V AC [3]. Check the input voltage of the model you choose, though: if its datasheet does not list 600 V, a step-down transformer is needed upstream, and the site drawing should show it. Our guide to single-phase vs three-phase UPS covers Canadian service voltages and the current calculation.
Generators. On generator power, frequency can drift more than on the utility. A double-conversion UPS keeps a stable output frequency, but it may refuse to transfer to bypass if the bypass input is no longer synchronized. A unit in eco mode passes those variations through as long as they stay within its eco-mode window; most units leave eco mode automatically when the input goes out of tolerance [1]. Check the setting. Our article on generator and UPS compatibility covers the case.
Batteries. The valve-regulated lead-acid (VRLA) batteries in UPS units have a design life of 3 to 5 years depending on the environment, according to Schneider Electric [7], and APC’s Back-UPS Pro manual gives the same typical life [6]. A warm room or frequent outages shorten it. See our guide to the UPS battery as the critical component.
Method: reading a UPS diagram on site in six steps
- Identify the topology from the datasheet: standby, line-interactive, hybrid conversion or double conversion. The IEC 62040-3 class, when published, confirms it.
- Locate the sources on the one-line drawing: rectifier input, bypass input (same or separate source), generator, transformers.
- Locate the disconnecting devices and their normal state (open or closed), with their on-site labels.
- Read the current mode on the display or monitoring software: online, eco, battery, bypass. The mode tells you which path is feeding the load now.
- Check the batteries: string voltage, installation date, result of the last self-test or runtime test. The UPS runtime calculator gives an estimate; a load bank test gives the real value.
- Read the event log: transfers to bypass, battery events, alarms. Repeated transfers to bypass are a sign to investigate.
Failure modes and safety boundaries
The diagram helps predict how the unit will fail:
- Batteries at end of life. On a standby or line-interactive unit, a weak battery only shows up when utility power fails and the load drops. On a double-conversion unit, the load keeps running through the rectifier and inverter while utility power is present, but the real runtime may be zero. Only a test shows it.
- Inverter fault. On a double-conversion unit with a static bypass, the load moves to raw utility power. The unit appears to run while the protection is gone.
- Bypass not available. If the bypass input is out of tolerance (generator, disturbed supply) when the inverter faults, the load can drop.
- Switching error. A maintenance bypass operated out of sequence can drop the load or parallel two sources. The manufacturer’s sequence applies without exception.
Safety boundary: a UPS holds stored energy. APC’s manual states that it may present a shock hazard even when disconnected, and that wiring is for a qualified electrician [6]. In Canada, work near energized parts falls under CSA Z462, the workplace electrical safety standard [4]. The checks in this guide are done from the outside, at the display and in the log. Opening panels and operating bypass switches are for a technician trained on the model.
Checklist and records to keep
- The topology of each UPS is known and recorded in the equipment register.
- The expected normal mode is defined (online or eco) and the display confirms it.
- The one-line drawing shows the rectifier input, bypass input, maintenance bypass and battery cabinets.
- The manufacturer’s maintenance bypass sequence is posted near the cabinet.
- The battery installation date is known; the age is compared with the 3 to 5 year VRLA design life [7].
- A recent runtime test exists for critical loads.
- Behaviour on generator has been checked, bypass included.
- Bypass and battery alarms reach someone who acts on them.
Records to keep
| Record | Why |
|---|---|
| Current one-line drawing | Shows the actual sources, bypasses and disconnecting devices |
| Model datasheet and manual | Topology, IEC class, switching sequences, safety instructions |
| Battery register | Installation date, per-block readings, runtime tests |
| Exported event log | History of transfers to bypass and to battery |
| Preventive maintenance reports | Proof of the checks; see our preventive UPS maintenance checklist |
For buying a small unit, UPSPLUSBATTERY’s comparison of line-interactive vs online UPS for a business lists models in both topologies, and the store carries APC RBC replacement battery cartridges.
Sources
- Schneider Electric, Energy Management Research Center, The Different Types of UPS Systems, White Paper 1, version 10, 2024. se.com
- IEC 62040-3:2021, Uninterruptible power systems (UPS), Part 3: Method of specifying the performance and test requirements, International Electrotechnical Commission. webstore.iec.ch
- CSA Group, CSA C22.2 No. 107.3:14 (R2024), Uninterruptible power systems, binational standard with UL 1778. csagroup.org
- CSA Group, CSA Z462, Workplace electrical safety. csagroup.org
- Eaton, C. Loeffler, Which UPS is right for the job?, White Paper WP09-19, 2009 (archived copy).
- Schneider Electric, Back-UPS Pro User Guide, JPT92208, April 2026. se.com
- Schneider Electric, FAQ FA158828, sealed lead-acid (VRLA) batteries in APC UPS units. apc.com
Next step
Do you have a UPS whose mode or diagram does not match what you expected, repeated transfers to bypass, or batteries of unknown age? Our technicians work on all major brands across Canada. See our UPS preventive maintenance service or request service.


